PEER CONSTRUCTIONS INTRANET

Small bore wastewater and macerator pump installation procedure

Under the Work Health and Safety Act 2012 (SA) employees must take reasonable care of their own health and safety. PEER Construction is committed to ensuring everyone who may be affected by the organisation’s activities are safe.

Purpose

The purpose of this procedure is to provide guidance on how to install a small bore wastewater and macerator pump procedure

This procedure applies to activities carried out at PEER Construction sites.

Legislative requirements

Small bore macerator pump installations must meet the performance requirements of the National Construction Code Volume 3 – Plumbing Code of Australia (PCA). The performance requirements of the PCA must comply with AS/NZS 3500.2:2015 – Sanitary plumbing and drainage standard. Refer to Part C of the PCA for further information on sanitary plumbing and drainage systems, and the ‘deemed to satisfy’ provisions.

Installing small bore wastewater and macerator pumps

When installing small bore wastewater and macerator pumps that receive discharge from one or more waste fixtures, ensure that:

  • pumps are only allowed when it is not practicable to gravitate to a sewer connection
  • plumbing fixtures in a new building must gravitate to the plumbing system, except those installed in a basement
  • the pump apparatus must be positioned next to the fixture, in the same room
  • the pump apparatus must have removable, appropriately sized airtight covers, for maintenance purposes
  • the pumping apparatus must have a vent of at least 50 mm that vents into the atmosphere.
Venting of small bore pump apparatus
AS/NZS 3500.2 does not address small bore pumping apparatuses that do not hold a volume of water at any time. The Office of the Technical Regulator (OTR) recommend, where possible, all pump chambers have a vent installed to atmosphere.

In cases where venting to atmosphere is not possible, and the small-bore pumping apparatus does not hold a volume of water at any time, manufacturers may specify optional alternative venting arrangements such as a carbon filter vent.

Alternative venting will only be acceptable for dry, no reservoir, small-bore pumping apparatus which receive either one kitchen sink or one hand basin. All alternative venting products must be watermarked and meet the manufacturer’s specifications and instructions.

Pumped discharge pipework

Pump discharge pipes must comply with AS/NZS 3500.2:2015 and discharge to one of the following locations:

  • an inspection chamber
  • a boundary trap shaft
  • a stack below the lowest fixture connection on any floor
  • a drain or combined discharge pipe, providing the connection is at least 2.5 metres from any other connection
  • downstream of a reflux valve, or at least 2.5 metres upstream of a reflux valve
  • a minimum of 1 metre downstream of a boundary trap.
Discharge pumps or rising mains
Discharge pumps or rising mains will only be permitted by the Office of the Technical Regulator (OTR) when it is not practicable to gravitate to a sewer connection.

The National Construction Code Series Volume Three, Plumbing Code of Australia (PCA), Part C2 specifies the objectives and performance requirements relating to installing sanitary drainage systems. AS/NZS 3500.2 and AS/NZS 3500.5

Sanitary plumbing and drainage are the ‘deemed to satisfy’ documents listed in Part C2 of the PCA, which contains sections on pumped discharges and rising mains.

Installing discharge pumps

The pumping method will include a wet well (including submersible pump), holding tank (with pump) or small bore macerator type unit.

  • Wet wells must be fit for purpose and installed in accessible positions.
  • Holding tanks must be constructed of authorised materials including precast or cast in situ concrete, corrosion resistant metals or glass reinforced plastics.
  • Covers must have access openings, with removable airtight covers sized for maintenance purposes.
Maximum flow rate

Plumbers must contact SA Water (opens in new window) to find out the maximum flow rate from a pump into a sewer connection.

Discharge locations

The outlet pipe from the wet well or holding tank must discharge to one of the following:

  • an inspection chamber
  • a boundary trap shaft
  • a stack below the lowest connection on any floor
  • a drain or combined discharge pipe, providing the connection is at least 2.5 metres from any other connection
  • downstream of a reflux valve or at least 2.5 metres upstream of a reflux valve
  • a minimum of 1 metre downstream of a boundary trap
  • directly to the water entity’s sewer, where approved by the entity.
Choice of material and identifying pump discharge pipe or rising main
  • Materials used for the discharge pipe or rising main from a wet well or holding tank must be fit for purpose and shall comply with the relevant parts of Section 2 of AS/NZS 3500.1.
  • Buried discharge pipes or rising mains must be enclosed in a sleeve or continually spirally wrapped with identification tape. The sleeving or spiral wrapping must be identified for the full length with the wording ‘sewer rising main’ or ‘pumped discharge pipe’ in accordance with AS 1345.
  • Above ground discharge pipes or rising mains must be identified in accordance with AS 1345.
  • Identification tape with the wording ‘sewer rising main’ or ‘pumped discharge pipe’ must be installed on the pipe in a visible position along the length of the pipe (not wrapped around it) and fastened to the pipe no less than every 3 metres.
Certificates of Compliance

Plumbers must provide a certificate of compliance to the customer and the Office of the Technical Regulator (OTR) within 7 days of finishing plumbing work, except for:

  • changing tap washers
  • clearing blocked sanitary drainage pipework not exceeding 50 mm in diameter
  • replacing, altering, repairing, maintaining, or disconnecting domestic tapware.

Penalties for not supplying a plumbing Certificate of Compliance include warnings, disciplinary interviews, and potential legal action, and are detailed in the Water Industry Act 2012.

Performance solutions

When it is not possible to have a 50 mm vent discharging into the atmosphere, plumbers must send a performance solution detailing the alternative venting method to the OTR.

Performance solutions aren’t permitted when soil fixtures are connected to the pump apparatus. An alternative venting method must achieve the same outcome as the requirement for a vent to the atmosphere.

Performance solutions sent to the OTR must include:

  • A covering letter from a recognised expert, e.g. pump manufacturer or hydraulic consultant, outlining the proposed performance solution and how it meets the performance requirements of the PCA. If carbon filters or other venting methods are included as a component of the performance solution, a maintenance schedule for the venting method must also be included.
  • A letter from the property owner accepting the performance solution and confirming they will do the necessary scheduled maintenance.

The OTR will send a Notice of Advice letter confirming the performance solution to the property owner. The Notice of Advice will be registered on the South Australian Integrated Land Information System and provided to any interested party on request.

Work Health and Safety Act 2012 (SA)
Work Health and Safety Regulations 2012 (SA)
Environment Protection Act 1993
Water Industry Act 2012
WHS policies and procedures

Version 1.0 – Last updated 19/2/2022